Section 5: Con guring Binary Inputs
GPC-XP Controller Technical Guide
18
Con guring Binary Inputs
Left-click on the “ON” or “OFF” button to the right of Binary Input
#1 in the Binary Input Window (Figure 24, page 17) to open the
Binary Input Con guration Window (Figure 26 below). Each Binary
Input is separately con gured, so 8 binary input combinations are
possible in one controller.
Binary Con guration
The following con gurations are available for each Binary Input:
Not Used
N/O Contact (Close for Active) - This normally open
(N/O) input will become active when 24 VAC is applied.
N/C Contact (Open for Active) - This normally closed
(N/C) input will become active when 24 VAC is removed.
Read Global Binary - This input will read the Global
Binary on the selected channel. Click on the Question Mark
symbol for Help information. See Figure 111, page 48 in
the Appendix for the Global Binary Help Screen.
Push-Button Override - If a discrete Push-Button
Override switch (not on a space sensor) is wired to this
input, also select the Override Duration desired (up to
24 hours). An Override on Binary Input #1 would affect
Schedule #1. An Override on Binary Input #2 would affect
Schedule #2, etc.
Follow Relay - This input will be active when the selected
relay is ON.
Figure 26: Binary Input Con guration Window