Programming
21
HB Controller Technical Guide
Heating Fan Off Delay
Description Min. Default Max.
Fan Off Delay Period 1 Sec 120 Sec 180 Sec
The Heating Fan Off Delay is a factory setting and should not be
changed unless authorized to do so by WattMaster or AAON
®
Techni-
cal Support.
Auto Stage-Up Time
Description Min. Default Max.
Auto Staging Up Delay 180 Sec 600 Sec 900 Sec
The Auto Stage-Up Time can be adjusted on this screen when you are
using a single-stage thermostat with a multi-stage HB unit.
Economizer Module Status Screens
The Economizer Module Status Screens are accessed by navigating to
the Economizer Module and pressing the ENTER key. The following
screen will then appear:
Select “Status” by pressing the ENTER key. Press the up and down
SELECT arrow keys to move forward and backward through the
Economizer Module Status screens.
Economizer Current Position
Line #2 displays the current Economizer Position as a percent open
value.
Supply Air Temperature
Line #2 displays the current Supply Air Temperature.
Programming with the HB Service Tool
Heating Minimum Off Time
Description Min. Default Max.
Minimum Off Time 60 Sec 60 Sec 900 Sec
Adjust the desired Heating Minimum Off Time and then press the
ENTER key.
Heating Minimum On Time
Description Min. Default Max.
Minimum On Time 120 Sec 120 Sec 900 Sec
Adjust the desired Heating Minimum On Time and then press the
ENTER key.
Heating Stage-Up Delay
Description Min. Default Max.
Staging Up Delay Interval 180 Sec 180 Sec 900 Sec
Adjust the desired Heating Stage-Up Delay time and then press the
ENTER key.
Heating Stage Down Delay
Description Min. Default Max.
Staging Down Delay Interval 60 Sec 60 Sec 900 Sec
Adjust the desired Heating Stage Down Delay time and then press the
ENTER key.
Heat Safety Monitor Maximum Trips
Description Min. Default Max.
Heat Safety Maximum Count 1 3 5
The Heating Safety Maximum Trips is a factory setting and should
not be changed unless authorized to do so by WattMaster or AAON
®
Technical Support.