PREHEAT-X Technical Guide
LCD DISPLAY SCREENS
19
SCALING
DEG. F
DEG. C
TEMPERATURE SCALE
Fahrenheit (default) or Celsius.
This setting is used only in stand-alone mode.
STG UP
0-1200 SECONDS
STAGE UP DELAY
If con gured for SCR modulation, this is the amount of time (in sec-
onds) the controller must wait to activate an additional stage of heat if
the Min Off Time is met. Range is 0 - 1200. Default is 180.
STG DWN
0-1200 SECONDS
STAGE DOWN DELAY
If con gured for SCR modulation, This is the amount of time (in sec-
onds)the controller must wait to deactivate a stage of heat if the Min
Run time is met. Range is 0 - 1200. Default is 180.
MIN RUN
0-1200 SECONDS
MINIMUM RUN TIME
This is the amount of time (in seconds) a stage of heat must remain on
before it can be deactivated. Range is 0 - 1200. Default is 120.
MIN OFF
0-1200 SECONDS
MINIMUM OFF TIME
This is the amount of time (in seconds) a stage of heat must remain off
before it can be activated. Range is 0 - 1200. Default is 60.