VCM-X Component & Systems Wiring
123
Miscellaneous Diagrams and Technical Information
Sensor Checks
The following sensor voltage and resistance tables are provided to aid in checking
sensors that appear to be operating incorrectly. Many system operating problems
can be traced to incorrect sensor wiring. Be sure all sensors are wired per the
wiring diagrams in this manual.
If the sensors still do not appear to be operating or reading correctly, check voltage
and/or resistance to con rm that the sensor is operating correctly per the tables.
Please follow the notes and instructions below each chart when checking sensors.
Temperature & Humidity Sensor Voltage-Resistance Table
Thermistor Sensor Testing Instructions
Use the resistance column to check the thermistor sensor while
disconnected from the controllers (not powered). Use the voltage
column to check sensors while connected to powered controllers.
Read voltage with meter set on DC volts.
Place the “-”(minus) lead on GND terminal and the “+”(plus) lead
on the sensor input terminal being investigated.
If the voltage is above 5.08 VDC, then the sensor or wiring is “open.”
If the voltage is less than 0.05 VDC, the sensor or wiring is shorted.
Temperature – Resistance – Voltage For Type III 10 K Ohm Thermistor Sensors
Temp
(°F)
Resistance
(Ohms)
Voltage
@
Input
(VDC)
Temp
(°F)
Resistance
(Ohms)
Voltage
@
Input
(VDC)
Temp
(°F)
Resistance
(Ohms)
Voltage
@
Input
(VDC)
-10 93333 4.620 60 14681 3.042 86 8153 2.297
-5 80531 4.550 62 14014 2.985 88 7805 2.242
0 69822 4.474 64 13382 2.927 90 7472 2.187
5 60552 4.390 66 12758 2.867 95 6716 2.055
10 52500 4.297 68 12191 2.810 100 6047 1.927
15 45902 4.200 69 11906 2.780 105 5453 1.805
20 40147 4.095 70 11652 2.752 110 4923 1.687
25 35165 3.982 71 11379 2.722 115 4449 1.575
30 30805 3.862 72 11136 2.695 120 4030 1.469
35 27140 3.737 73 10878 2.665 125 3656 1.369
40 23874 3.605 74 10625 2.635 130 3317 1.274
45 21094 3.470 75 10398 2.607 135 3015 1.185
50 18655 3.330 76 10158 2.577 140 2743 1.101
52 17799 3.275 78 9711 2.520 145 2502 1.024
54 16956 3.217 80 9302 2.465 150 2288 0.952
56 16164 3.160 82 8893 2.407
58 15385 3.100 84 8514 2.352
Zobrazit stránku 122

Komentáře k této Příručce

Žádné komentáře

Campbell-scientific SR50-L CSC Ultrasonic Distance Sensor manuales

Manuales del propietario y guías del usuario para Sensores Campbell-scientific SR50-L CSC Ultrasonic Distance Sensor.
Ofrecemos 1 manuales en pdf Campbell-scientific SR50-L CSC Ultrasonic Distance Sensor para descargar gratis por tipos de documentos: Manual de usuario






Más productos y manuales para Sensores Campbell-scientific

Modelos Tipo de documento
SS100 Sensor Simulator Manual de usuario   Campbell Scientific SS100 Sensor Simulator User Manual, 10 paginas
ST350 Strain Transducer for Structural Testing Manual de usuario   Campbell Scientific ST350 Strain Transducer for Structural Testing User Manual, 50 paginas
TE525-LC Precipitation Sensor for MetData1 Manual de usuario   Campbell Scientific TE525-LC Precipitation Sensor for MetData1 User Manual, 4 paginas
Wireless Sensor Network (CWB100, CWS220, and CWS90 Manual de usuario   Campbell Scientific Wireless Sensor Network (CWB100, CWS220, and CWS900) User Manual, 70 paginas