PT-Link II Interface
PT-Link II BACnet
®
Technical Guide
53
Appendix H - VCM BACnet Parameters
BACnet Properties for the VCM Controller
Parameter Name Object Description Limits
Bypass
Damper
Position
ByPasDmp AI: 153 Current position
of the bypass
damper signal.
Return
Damper
Position
RaDmp AI: 154 Current position
of the return
damper signal.
Outdoor Air
Dewpoint
OaDwpt AI: 47 Current calcu-
lated outdoor air
dewpoint added
on version 1.09.
Current
Supply Air
Setpoint
SaTpStM AI: 82 Current SAT
Cooling or Heat-
ing setpoint if
there is no reset
source; Current
calculated SAT
setpoint with
Reset Source.
Coil
Temperature
CoilTp AI: 181 Current coil
temperature
reading added on
version 1.09.
Preheater
Setpoint
PreHtSp AV: 196 Low Outside Air
Ambient
Protection
Setpoint
0 100
CO
2
Setpoint
CO2St AV: 149 When the CO
2
level rises
above the CO
2
Protection Limit
Max Level, the
Economizer’s
Minimum Posi-
tion will begin
to reset open
proportion-
ally between the
CO
2
Protection
Limit Max Level
Setpoint and
the Reset Range
Setpoint.
0 3000
Static
Pressure
Setpoint
DuctPrSt AV: 152 This is the target
duct pressure to
be maintained by
the VFD blower
signal.
0.01 3
Minimum
Outside Air
Setpoint
MinEcoSt AV: 151 This is the
minimum
position of the
economizer in
the occupied
modes.
1 100
BACnet Properties for the VCM Controller
Parameter Name Object Description Limits
Occupied/
Mode
Enable
Cooling
Setpoint
OcpClSt AV: 42 If the control
temperature rises
one degree above
this setpoint,
the control will
activate the
cooling demand.
If the control
temperature is
the Supply Air
Sensor, then the
cooling demand
is always active.
099
Occupied/
Mode
Enable
Heating
Setpoint
OcpHtSt AV: 43 If the control
temperature
drops one degree
below
this setpoint,
the control will
activate the
heating demand.
If the
control
temperature
is the Supply
Air Sensor, then
there is no heat-
ing demand.
099
Outdoor Air
Sensor Offset
OaTpOst AV: 53 If the Outdoor
Temperature
Sensor is reading
incorrectly, you
can use this op-
tion to
enter an offset
temperature to
adjust the Sen-
sor’s Tempera-
ture.
-100 100
Relief
Pressure
Setpoint
RfPrSt AV: 118 This is the target
building pressure
to be maintained
by the VFD
Relief signal.
-0.2 0.2
Return Air
Sensor Offset
RaTpOst AV: 65 If the Return
Temperature
Sensor is read-
ing incorrectly,
you can use this
option to enter
an offset tem-
perature to adjust
the Sensor’s
Temperature.
-100 100