Orion-system VCC-X Controller Uživatelský manuál Strana 52

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 96
  • Tabulka s obsahem
  • ŘEŠENÍ PROBLÉMŮ
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 51
VCC-X SETPOINTS
VCC-X Operator Interface SD
52
Setpoint Screen #46 - Space Sensor
Calibration - Current and Offset
VCC-X Spts ID:#
Space Sensor Cal
Current: 0.0ºF
Offset.: 0.0ºF
If the Space Air Temperature Sensor is reading incorrectly, you can
use this option to enter an offset temperature to adjust the Sensor’s
Temperature. Line 3 will display the current Space Air Temperature
reading. Enter a positive Sensor Calibration value in Line 4 to raise
the Space Temperature Sensor reading or a negative value in Line
4 to lower the Sensor reading.
Description Minimum Default Maximum
Space Sensor
Calibration Offset
-100.0ºF
(-55.5ºC)
0.0ºF
(0ºC)
100.0ºF
(55.5ºC)
Setpoint Screen #47 - Return Air Temperature
Sensor Calibration - Current and Offset
VCC-X Spts ID:#
Return Sensor Cal
Current: 0.0ºF
Offset.: 0.0ºF
If the Return Air Temperature Sensor is reading incorrectly, you can
use this option to enter an offset temperature to adjust the Sensor’s
Temperature. Line 3 will display the current Return Air Temperature
reading. Enter a positive Sensor Calibration value in Line 4 to raise
the Return Temperature Sensor reading or a negative value in Line
4 to lower the Sensor reading.
Description Minimum Default Maximum
Return Air Sensor
Calibration Offset
-100.0ºF
(-55.5ºC)
0.0ºF
(0ºC)
100.0ºF
(55.5ºC)
Setpoint Screen #48 - SAT Sensor Calibration
- Current and Offset
VCC-X Spts ID:#
SAT Sensor Cal
Current: 0.0ºF
Offset.: 0.0ºF
If the Supply Air Temperature Sensor is reading incorrectly, you can
use this option to enter an offset temperature to adjust the Sensor’s
Temperature. Line 3 will display the current Supply Air Temperature
Sensor reading. Enter a positive Sensor Calibration value in Line
4 to raise the Supply Air Temperature Sensor reading or a negative
value in Line 4 to lower the Sensor reading.
Description Minimum Default Maximum
Sensor Calibration SAT -100.0ºF
(-55.5ºC)
0.0ºF
(0ºC)
100.0ºF
(55.5ºC)
VCC-X Setpoint Screens
Zobrazit stránku 51
1 2 ... 47 48 49 50 51 52 53 54 55 56 57 ... 95 96

Komentáře k této Příručce

Žádné komentáře